The 512/524 and 1712/1724 EPGs are three-component governing systems for 12 or 24 Vdc operation
All EPG systems include an actuator, an electronic speed control, and magnetic pickup
Isochronous electronic controls are available with either start-fuel limit or with switchselected dual dynamics
Droop controls are available for certain types of parallel generator application
Load sharing devices are available for use with the isochronous models used in paralleled applications
The selected EPG actuator is mounted on the prime mover and mechanically linked to the fuel control
The rotary design and output shaft on both ends gives 30° (512/524) or 35° (1712/1724) clockwise or counterclockwise travel to low-mass, lowfriction fuel linkages
Preloaded internal return springs supply the shaft torque in the decrease-fuel direction and for shutdown should the electronic control signal be lost
A rugged cast aluminum housing permits installation of the speed control on the engine skid
In operation, the control compares the speed of the engine with the desired speed or desired load and sets the actuator position to correct discrepancies
Gain and stability adjustments tailor the governor’s response to the specific engine
EPG controllers with switch-selected dynamics allow stable operation at no load and brisk response when the unit is heavily loaded